Plan Review Notes For Permit 02090718 |
Permit Number |
02090718 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-28 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) PLEASE PROVIDE A SANITARY AND A WATER | | RISER DIAGRAM. | | 2) PLEASE PROVIDE DETAIL FOR ACCESSIBLE | | TOILET ROOM AND FOR DRINKING FOUNTAIN. | | SHOW COMPLIANCE WITH 11-4.22 AND ALL | | SUBSECTIONS. ALSO SHOW COMPLIANCE WITH | | 11-4.15 AND ALL SUBSECTIONS INCLUDING | | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO | | HAVE DIFFICULTY BENDING OR STOOPING. | | 3) ALL SHEETS OF A SIGNED AND SEALED SET | | OF PLANS SHALL BE SIGNED AND SEALED BY | | ENGINEER/ARCHITECT OF RECORD. (SEE SHEET | | SHOWING DRINKING FOUNTAIN LOCATION) | | 4) NO INFORMATION GIVEN FOR ROOF PRIMARY | | AND SECONDARY DRAINS. PLEASE SUBMIT | | CALCULATIONS FOR EACH PER 1106 AND 1107 | | 5) PLEASE INDICATE TYPE OF MATERIAL TO | | BE STORED ON SECOND FLOOR. OTHER REVIEW | | COMMENTS MAY RESULT ACCORDING TO INFOR- | | ATION GIVEN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|