2002-10-07 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS
 FOR EXIT AND EMGERGENCY LTS. 700-12
  
 2)NOTE: PLEASE PROVIDE CIRCUTIING ON
 PLANS AND CORRELATE W/ SUBMITTED PANEL
 SCHEDULE.
  
 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 -ING METHOD BETWEEN MAIN AND SUB-PANEL.
 SIZE PER 250-122
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS, PANELS, BRKRS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9
  
 5)NOTE: PLEASE CLARIFY SIZE FOR SERVICE
 ENTRANCE CONDUCTORS. SHOWN AS 3-3/10`S
 ? 310-16
  
 6)NOTE: PLEASE SHOW RECEPT FOR A/C UNIT
 210-63.
  
 7)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 215-3,230-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  