Plan Review Notes
Plan Review Notes For Permit 02090682
Permit Number 02090682
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-09-17 00:00:001) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C. ONLY CLASS A, STYLE D IS
 PERMITTED.
  
 2) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHT FIXTURES IN HALLWAY.
  
 3) DOES THE EXISTING SMOKE DETECTOR IN
 THE ELEVATOR LOBBY PROVIDE PHASE ONE
 PHASE TWO ELEVATOR RECALL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910