Plan Review Notes
Plan Review Notes For Permit 02090681
Permit Number 02090681
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-09-17 00:00:001) PLANS INDICATE THAT THE FIRE ALARM
 SYSTEM IS CLASS B STYLE C. CLASS A OR
 ADDRESSABLE SYSTEMS ARE PERMITTED.
  
 2) PLANS DO NOT INDICATE THE LOCATION
 OF EMERGENCY LIGHTING IN CORRIDOR.
  
 3) INSTALLATION OF FIRE DAMPERS REQUIRE
 ACCESS DOORS.
  
 4) DOES THE EXISTING SMOKE DETECTOR
 LOCATED OUTSIDE THE ELEVATOR INITIATE
 PHASE-1,2 ELEVATOR RECALL?
  
 MIKE WENNERGREN, ACTING CAPTAIN
 659-8096, EXT.8497
 835-2910