Plan Review Notes For Permit 02090681 |
Permit Number |
02090681 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-17 00:00:00 | 1) PLANS INDICATE THAT THE FIRE ALARM | | SYSTEM IS CLASS B STYLE C. CLASS A OR | | ADDRESSABLE SYSTEMS ARE PERMITTED. | | | | 2) PLANS DO NOT INDICATE THE LOCATION | | OF EMERGENCY LIGHTING IN CORRIDOR. | | | | 3) INSTALLATION OF FIRE DAMPERS REQUIRE | | ACCESS DOORS. | | | | 4) DOES THE EXISTING SMOKE DETECTOR | | LOCATED OUTSIDE THE ELEVATOR INITIATE | | PHASE-1,2 ELEVATOR RECALL? | | | | MIKE WENNERGREN, ACTING CAPTAIN | | 659-8096, EXT.8497 | | 835-2910 |
|