Plan Review Notes For Permit 02090679 |
Permit Number |
02090679 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-20 00:00:00 | THE SIDE LIGHT SHOWN AS (C) NEAR DOOR | | 201 DOES NOT COMPLY WITH FBC 705.1.3.7. | | PLEASE REVISE AS NECESSARY. | | | | TWO EXIT DOORS ARE REQUIRED FROM THIS | | SPACE IN ACCORDANCE WITH FBC 1004.1.2. | | TRAVEL DISTANCE, (NOT COMMON PATH), | | EXCEEDS 75'.SEE ALSO FBC 1004.1.4. | | | | NOTES TO DOOR 201 SPECIFY AN ELECTRIC | | DEADBOLT.THE LOCKING ARRANGEMENTS ON | | REQUIRED EXIT DOORS MUST COMPLY WITH | | FBC 1012.1.7 |
|