Plan Review Notes
Plan Review Notes For Permit 02090646
Permit Number 02090646
Review Stop P
Sequence Number 3
Notes
Date Text
2003-04-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 FROM PREVIOUS REVIEW: SHT 2 0F 3 UNIT #5
 LAV AND KITCHEN SINK SHALL NOT BE ON THE
 SAME RISER, (DIFFERENT WALLS).
 FROM PREVIOUS REVIEW: 2ND FLOOR UNIT #6
 SHALL TIE IN DOWNSTREAM OF BATHROOM FOR
 UNIT #5
 KITCHEN MOVED TO BATHROOM GROUP IN BATH
 #1 SHALL NOT DRAIN INTO THE WET VENTED
 BATHROOM GROUP PER SECTION 909.1
 BATH #5 HAS A HORIZONTAL DRY VENT. THIS
 IS NOT APPROVED PER SECTION 905.3
 KITCHEN SINK IN UNIT #6 SHALL NOT DRAIN
 INTO THE BATHROOM GROUP. SECTION 909.1
 KITCHEN SINK IN UNIT #2 SHALL NOT DRAIN
 INTO THE BATHROOM GROUP. SECTION 909.1
  