Plan Review Notes
Plan Review Notes For Permit 02090646
Permit Number 02090646
Review Stop P
Sequence Number 2
Notes
Date Text
2003-01-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: PLEASE SHOW
 COMPLIANCE WITH THE FAIR HOUSING ACT
 REQUIREMENTS 1 THRU 7. INDICATE SPECI-
 FICATION "A" OR "B" FOR EACH BATHROOM IN
 UNITS 1,2,4, & 5. SHOW BACKING AND CLEAR
 FLOOR SPACE FOR REQUIRED FIXTURES.
 2) FROM PRIVIOUS REVIEW: SHT 2 OF 3, IN-
 DICATE LOCATION OF PRIMARY AND SECONDARY
 ROOF DRAINS. INDICATE SQUARE FOOTAGE OF
 ROOF BEING DRAINED INCLUDING 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPET
 WALLS. SHOW SIZE OF PRIMARY AND SECOND-
 ARY ROOF DRAINS.
 3) SHT 2 0F 3 SANITARY RISER DIAGRAM
 DOES NOT MEET CODE. UNIT #5 LAV AND KIT.
 SINK SHALL NOT BE ON SAME RISER, (DIFF-
 ERENT WALLS. PLEASE MOVE LAV TO WHERE
 INDICATED). 2ND FLOOR UNIT #6 SHALL TIE
 IN DOWNSTREAM OF BATHROOM FOR UNIT #5.
 FLOOR DRAIN REQUIRED FOR LAUNDRY ROOM.
 KITCHEN FOR UNIT #1 SHALL BE LOCATED
 NEAR BATHROOM WHERE DRY HORIZONTAL VENT
 IS NOT LOCATED. KITCHEN FOR UNIT #6 IS
 NOT SHOWN AND SHALL BE SHOWN AS ON THE
 2ND FLOOR.
 4) SHT 2 OF 3, LAV FOR UNIT #6 IS NOT
 SHOWN ON FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377