2003-01-29 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| |
| 1) FROM PREVIOUS REVIEW: PLEASE SHOW |
| COMPLIANCE WITH THE FAIR HOUSING ACT |
| REQUIREMENTS 1 THRU 7. INDICATE SPECI- |
| FICATION "A" OR "B" FOR EACH BATHROOM IN |
| UNITS 1,2,4, & 5. SHOW BACKING AND CLEAR |
| FLOOR SPACE FOR REQUIRED FIXTURES. |
| 2) FROM PRIVIOUS REVIEW: SHT 2 OF 3, IN- |
| DICATE LOCATION OF PRIMARY AND SECONDARY |
| ROOF DRAINS. INDICATE SQUARE FOOTAGE OF |
| ROOF BEING DRAINED INCLUDING 1/2 AREA |
| OF ALL VERTICAL WALLS INCLUDING PARAPET |
| WALLS. SHOW SIZE OF PRIMARY AND SECOND- |
| ARY ROOF DRAINS. |
| 3) SHT 2 0F 3 SANITARY RISER DIAGRAM |
| DOES NOT MEET CODE. UNIT #5 LAV AND KIT. |
| SINK SHALL NOT BE ON SAME RISER, (DIFF- |
| ERENT WALLS. PLEASE MOVE LAV TO WHERE |
| INDICATED). 2ND FLOOR UNIT #6 SHALL TIE |
| IN DOWNSTREAM OF BATHROOM FOR UNIT #5. |
| FLOOR DRAIN REQUIRED FOR LAUNDRY ROOM. |
| KITCHEN FOR UNIT #1 SHALL BE LOCATED |
| NEAR BATHROOM WHERE DRY HORIZONTAL VENT |
| IS NOT LOCATED. KITCHEN FOR UNIT #6 IS |
| NOT SHOWN AND SHALL BE SHOWN AS ON THE |
| 2ND FLOOR. |
| 4) SHT 2 OF 3, LAV FOR UNIT #6 IS NOT |
| SHOWN ON FLOOR PLAN. |
| |