Notes |
Date |
Text |
2002-10-05 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) PLEASE SHOW COMPLIANCE WITH FAIR | | HOUSING ACT REQUIREMENTS 1 THRU 7. | | INDICATE SPECIFICATION "A" OR "B" FOR | | EACH BATHROOM IN UNITS 1, 2, 4, & 5. | | SHOW BACKING AND CLEAR FLOOR SPACE FOR | | REQUIRED FIXTURES. | | 2) SHT 2 OF 3, INDICATE LOCATION OF | | PRIMARY AND SECONDARY ROOF DRAINS. IN- | | DICATE SQUARE FOOTAGE OF ROOF BEING | | DRAINED, AND INCLUDE 1/2 AREA OF ALL | | VERTICAL WALLS. SHOW SIZE OF PRIMARY AND | | SECONDARY DRAINS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|