Plan Review Notes For Permit 02090646 |
Permit Number |
02090646 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-07 00:00:00 | *********** UNSAT******************* | | | | 1)NOTE: PLEASE NOTE ARC FAULT PROTECTION | | PER 210-12. | | | | 2)NOTE: PLEASE NOTE GROUNDING ELECTRODE | | SYSTEM IS SHOWN GOING TO FOOTER STEEL | | ON AN EXISTING BLDG. PLEASE NOTE IF | | SHOWN ON RISER THEN IT WOULD BE REQ`D TO | | BE INSTALLED, HOWEVER IF EXISTING | | FOOTER, IT WILL NOT BE REQ`D TO CUT | | CONCRETE. | | | | 3)NOTE: PLEASE CLARIFY RECEPTS PER | | 210-52E | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|