2003-01-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/12/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 5) --PROVISO--
 THE LENGTH OF THE REPLACEMENT WINDOWS
 SHALL BE WITHIN THE SCOPE OF THE
 SUBMITTED SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 01-0226.04
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORMS.THIS COMMENT HAS NOT BEEN
 ADDRESSED.THE SUBMITTED FORMS STILL
 REFER TO UNIT 3, WHICH DOES NOT EXIST.
 THEREFOR, THE INPUT DATA FOR UNIT 1 & 2
 DOES NOT REPRESENT THE ACTUAL FLOOR,
 WINDOW, WALL AREA ETC FOR THOSE UNITS.
 SEE NOTE BELOW.
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499