2002-11-12 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PROJECT DESCRIPTION ON THE PERMIT |
| APPLICATION FORM MAKES REFERENCE TO AN |
| ADDITION.AS THERE IS NO CORRESPONDING |
| REFERENCE TO AN ADDITION ON THE PLANS, |
| SHOULD THE PROPOSAL INCLUDE ADDITIONAL |
| FLOOR AREA, THEN AMENDED PLANS SHALL BE |
| SUBMITTED TO CLARIFY THE DIFFERENCE |
| BETWEEN EXISTING AND PROPOSED LAYOUT. |
| |
| 3) IF ADDITIONAL FLOOR AREA IS PROPOSED |
| (SEE COMMENT #2, ABOVE), THEN IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY, |
| THE PLANS STAMPED BY THEM AND A COPY OF |
| THE RECEIPT SUBMITTED TO CITY OF WEST |
| PALM BEACH CONSTRUCTION SERVICES DEPT |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 4) FBC 1005.4EGRESS WINDOWS.THE |
| REPLACEMENT WINDOWS FOR BEDROOM 2 OF |
| UNIT 1 AND BEDROOM 2 OF UNIT 2 SHALL BE |
| EGRESS WINDOWS WITH A MAXIMUM SILL |
| HEIGHT OF 44", MINIMUM CLEAR OPENING |
| WIDTH OF 20", MINIMUM CLEAR OPENING |
| HEIGHT OF 24" AND A MINIMUM NET CLEAR |
| OPENING OF 5.7 SQ FT (5.0 SQ FT FOR |
| GROUND FLOOR OPENINGS). |
| |
| 5) SUBMIT A WINDOW SCHEDULE OR |
| ELEVATIONS SHOWING WINDOW HEIGHTS AND |
| WINDOW PRESSURES TO VERIFY THAT THESE |
| ARE WITHIN THE SCOPE OF THE SUBMITTED |
| PRODUCT APPROVAL NOA# 01-0226.04 |
| |
| 6) FBC 13-103.0THE SUBMITTED ENERGY |
| CODE COMPLIANCE FORMS REFER TO UNITS 1, |
| 2 AND 3.SUBMIT FORMS WHICH CORRELATE |
| WITH THE SIZE AND NUMBER OF UNITS |
| PROPOSED. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |