Plan Review Notes
Plan Review Notes For Permit 02090645
Permit Number 02090645
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROJECT DESCRIPTION ON THE PERMIT
 APPLICATION FORM MAKES REFERENCE TO AN
 ADDITION.AS THERE IS NO CORRESPONDING
 REFERENCE TO AN ADDITION ON THE PLANS,
 SHOULD THE PROPOSAL INCLUDE ADDITIONAL
 FLOOR AREA, THEN AMENDED PLANS SHALL BE
 SUBMITTED TO CLARIFY THE DIFFERENCE
 BETWEEN EXISTING AND PROPOSED LAYOUT.
  
 3) IF ADDITIONAL FLOOR AREA IS PROPOSED
 (SEE COMMENT #2, ABOVE), THEN IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY,
 THE PLANS STAMPED BY THEM AND A COPY OF
 THE RECEIPT SUBMITTED TO CITY OF WEST
 PALM BEACH CONSTRUCTION SERVICES DEPT
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) FBC 1005.4EGRESS WINDOWS.THE
 REPLACEMENT WINDOWS FOR BEDROOM 2 OF
 UNIT 1 AND BEDROOM 2 OF UNIT 2 SHALL BE
 EGRESS WINDOWS WITH A MAXIMUM SILL
 HEIGHT OF 44", MINIMUM CLEAR OPENING
 WIDTH OF 20", MINIMUM CLEAR OPENING
 HEIGHT OF 24" AND A MINIMUM NET CLEAR
 OPENING OF 5.7 SQ FT (5.0 SQ FT FOR
 GROUND FLOOR OPENINGS).
  
 5) SUBMIT A WINDOW SCHEDULE OR
 ELEVATIONS SHOWING WINDOW HEIGHTS AND
 WINDOW PRESSURES TO VERIFY THAT THESE
 ARE WITHIN THE SCOPE OF THE SUBMITTED
 PRODUCT APPROVAL NOA# 01-0226.04
  
 6) FBC 13-103.0THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS REFER TO UNITS 1,
 2 AND 3.SUBMIT FORMS WHICH CORRELATE
 WITH THE SIZE AND NUMBER OF UNITS
 PROPOSED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499