Plan Review Notes
Plan Review Notes For Permit 02090643
Permit Number 02090643
Review Stop E
Sequence Number 3
Notes
Date Text
2003-01-30 00:00:00*************** UNSAT **************
  
 PLEASE NOTE, THERE ARE MANY ITEMS
 FROM FIRST TWO REVIEWS NOT DONE.
 PLEASE SEE ATTACHED LETTER FOR FS 553-80
  
 1)NOTE: PLANS HAVE BEEN REVISED NOW
 SHOWING LAUNDRY CIRCUIT, HOWEVER PER
 210-11-C2 MUST BE A MIN 1500KW.
 210-52
  
 2)NOTE: PLANS STILL MISSING OUTLETS
 LISTED PER 210-12 ON PANEL SCHEDULE.
 ALSO 210-52,210-52E
  
 3)NOTE: PLEASE SEE ELECTRICAL NOTES
 MENTIONING A/C UNIT DISC'S TO BE 50A`S??
 PLEASE CLARIFY WHERE A/C'S UNIT ARE
 SHOWN ON PLANS??
  
 PLEASE SEE ANY PREVIOUS NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE ALSO NOTE A 4X FEE WILL BE
 ACCESSED IF NOTES ARE NOT ADDRESSED FOR
 PLAN REVIEW.PER FS 553-80(2)(B)
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372