Plan Review Notes
Plan Review Notes For Permit 02090643
Permit Number 02090643
Review Stop P
Sequence Number 2
Notes
Date Text
2002-12-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW: LAUNDRY FACIL-
 ITIES REQUIRED PER TABLE 403.1
 2) SHT 2 OF 3 SANITARY RISER DIAGRAM,
 BATHROOMS FROM SECOND FLOOR SHALL NOT
 DRAIN THROUGH VENTS FROM FIRST FLOOR
 BATHROOMS IN UNITS 1,2,3,4. ONLY THE
 FIXTURES FROM THE BATHROOM GROUP SHALL
 DRAIN INTO THE WET VENT SYSTEM FOR THE
 BATHROOM. KITCHEN SINK SHALL DRAIN DOWN-
 STREAM OF BATHROOM GROUP. SECTION 909.1
 3) BACKFLOW IS REQUIRED ON WATER SERVICE
 IF UNITS ARE NOT INDIVIDUALLY METERED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377