2002-12-05 00:00:00 | *************** UNSAT ************* |
| |
| 1)NOTE: PLEASE NOTE, REVIEW IS DONE FOR |
| A COMPLETED SERVICE RISER. PLEASE NOTE, |
| MISSING AIC RATING FOR NEW SERVICE |
| EQUIPMENT. MAIN DISC'S , PANELS AND BRKR |
| -S ALL MUST BE RATED FOR THE AVAILABLE |
| FAULT CURRNT PER 110-9 |
| |
| 2)NOTE: PLEASE NOTE MISSING REQ'D |
| CIRCUITS PER 210-11C-2 (LAUNDRY) |
| |
| 3)NOTE: PLEASE NOTE, WATER HEATERS MAY |
| NOT BE IN STORAGE/CLOSETS W/ EASILY |
| IGNITABLE MATERIALS. PLEASE PROVIDE |
| SEPARATION.422-17 |
| |
| 4)NOTE: PLEASE NOTE ITMES FROM FIRST |
| REVIEW WERE NOT ADDRESSED. 210-52E/ |
| 210-12 |
| |
| PLEASE NOTE, FOOTER STEEL IS SHOWN ON |
| RISER, PLEASE NOTE, NOT REQ`D ON EXIST- |
| ING BLDG TO CUT CONCRETE FOR THIS.PLEASE |
| NOTE HOWEVER, IF SHOWN ON PLANS, THEN IT |
| WILL BE REQ`D. PLEASE ALSO NOTE |
| SERVICE CONDUCTORS ARE BEING SHOWN AT |
| FOUR TIMES LARGER THAN REQ`D PER 310-15 |
| PLEASE NOTE, THE ABOVE IS JUST A NOTE |
| AND DOES NOT REFLECT ANY CODE VIOLATIONS |
| IF CHANGED AT LATER DATE, A REVISION |
| WILL BE REQ`D. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |