2002-12-05 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, REVIEW IS DONE FOR
 A COMPLETED SERVICE RISER. PLEASE NOTE,
 MISSING AIC RATING FOR NEW SERVICE
 EQUIPMENT. MAIN DISC'S , PANELS AND BRKR
 -S ALL MUST BE RATED FOR THE AVAILABLE
 FAULT CURRNT PER 110-9
  
 2)NOTE: PLEASE NOTE MISSING REQ'D
 CIRCUITS PER 210-11C-2 (LAUNDRY)
  
 3)NOTE: PLEASE NOTE, WATER HEATERS MAY
 NOT BE IN STORAGE/CLOSETS W/ EASILY
 IGNITABLE MATERIALS. PLEASE PROVIDE
 SEPARATION.422-17
  
 4)NOTE: PLEASE NOTE ITMES FROM FIRST
 REVIEW WERE NOT ADDRESSED. 210-52E/
 210-12
  
 PLEASE NOTE, FOOTER STEEL IS SHOWN ON
 RISER, PLEASE NOTE, NOT REQ`D ON EXIST-
 ING BLDG TO CUT CONCRETE FOR THIS.PLEASE
 NOTE HOWEVER, IF SHOWN ON PLANS, THEN IT
 WILL BE REQ`D. PLEASE ALSO NOTE
 SERVICE CONDUCTORS ARE BEING SHOWN AT
 FOUR TIMES LARGER THAN REQ`D PER 310-15
 PLEASE NOTE, THE ABOVE IS JUST A NOTE
 AND DOES NOT REFLECT ANY CODE VIOLATIONS
 IF CHANGED AT LATER DATE, A REVISION
 WILL BE REQ`D.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372