Plan Review Notes
Plan Review Notes For Permit 02090643
Permit Number 02090643
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-03 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO BE
 COMPLETED FOR FULL REVIEW.
 PLEASE NOTE MISSING SERVICE ENTRANCE
 CONDUCTORS. 215-5
  
 2)NOTE: PLEASE NOTE MISS RECEPTS PER
 210-52,210-52E.
  
 3)NOTE: PLEASE NOTE EQUIPMENT GROUNDING
 CONDUCTORS MISSING PER 250-122.
  
 4)NOTE: PLEASE NOTE RISR DIAGRAM SHOWS
 GUTTER FEEDING SERVICE AND YET PLANS
 SHOWS BEING SEPARATE? PLEASE CLARIFY AND
 NOTE 230-72.
  
 5)NOTE: PLEASE NOTE MISSING ARC FAULT
 PROTECTION. PER 210-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  