Plan Review Notes For Permit 02090643 |
Permit Number |
02090643 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-03 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE PLANS NEED TO BE | | COMPLETED FOR FULL REVIEW. | | PLEASE NOTE MISSING SERVICE ENTRANCE | | CONDUCTORS. 215-5 | | | | 2)NOTE: PLEASE NOTE MISS RECEPTS PER | | 210-52,210-52E. | | | | 3)NOTE: PLEASE NOTE EQUIPMENT GROUNDING | | CONDUCTORS MISSING PER 250-122. | | | | 4)NOTE: PLEASE NOTE RISR DIAGRAM SHOWS | | GUTTER FEEDING SERVICE AND YET PLANS | | SHOWS BEING SEPARATE? PLEASE CLARIFY AND | | NOTE 230-72. | | | | 5)NOTE: PLEASE NOTE MISSING ARC FAULT | | PROTECTION. PER 210-12. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|