Plan Review Notes
Plan Review Notes For Permit 02090643
Permit Number 02090643
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-01 00:00:00SHOW THE WIND PRESSURES +/- FOR THE
 WINDOWS AND ROOF COVERING.SEE FBC
 1606.1.7 #7.
  
 SHOW THE EXISTING OR PROVIDE NEW FIRE
 RATED TENANT SEPARATION.SEE FBC 704.3.
  
 SHOW THE EXISTING OR PROVIDE A FIRE
 RATED ENCLOSURE FOR THE INTERIOR STAIRS
 IN THE EAST BUILDING.SEE FBC 1006.1.1.
  
 SHOW THE EXISTING OR PROVIDE NEW,
 HANDRAILS ON EACH SIDE OF ALL THE
 STAIRS, IN BOTH BUILDINGS.SEE FBC
 1007.5.
  
 THE SURVEY SHOWS ONE STAIR ON THE WEST
 SIDE OF THE WEST BUILDING.THE PLANS
 SHOW STAIR WAYS ON THE WEST AND EAST
 SIDES. PLEASE CLARIFY DESIGN INTENT.
  
 THE EXTERIOR STAIRS MUST COMPLY WITH
 FBC 1006.2.2 FOR 3/4 HOUR PROTECTED
 OPENING EXPOSURE.PLEASE REVISE AS
 NECESSARY.
  
 NOTE CLEARLY THE EMERGENCY ESCAPE AND
 RESCUE OPENINGS FOR THE SLEEPING ROOMS
 IN ACCORDANCE WITH FBC 1005.4.1.