Plan Review Notes
Plan Review Notes For Permit 02090639
Permit Number 02090639
Review Stop R
Sequence Number 3
Notes
Date Text
2003-07-17 00:00:00REVISION DENIED BY BUILDING
  
 1) REVISED PLANS ARE REQUIRED TO BE
 SIGNED, SEALED AND DATED BY THE DESIGNER
 OF RECORD. THE ENGINEER'S TITLE BLOCK IS
 REQUIRED ON EACH SHEET OF THE PLAN.
  
 2) SUBMIT REVISED SHEETS A-3, S-1, AND
 E/M-1. CHANGES SHOULD BE CLOUDED AND
 NUMBERED. NUMBER OF REVISION AND DATE OF
 REVISION SHOULD BE LISTED IN UPPER RIGHT
 HAND SIDE OF THE SHEET.
  
 3) ROOMS NEED TO BE LABELED ON PLAN.
  
 4) PROVIDE THE WINDOW TYPE AND SIZE OF
 ALL WINDOWS THAT ARE CHANGED FROM THE
 PERMITED PLANS. EGRESS WINDOWS THAT
 COMPLY WITH FBC 1005.4 ARE REQUIRED AT
 ROOMS USED FOR SLEEPING.
  
 5) ANY CHANGES TO THE EXTERIOR (WINDOW
 LOCATION, ETC.) WILL HAVE TO BE REVIEWED
 AND APPROVED BY HISTORIC PRESERVATION
 DEPT.
  
 6) DRAWINGS AND SPECIFICATIONS SHOULD BE
 IDENTICAL TO THE PERMITTED SET EXCEPT
 FOR THE ITEMS THAT ARE BEING REVISED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714