Plan Review Notes
Plan Review Notes For Permit 02090639
Permit Number 02090639
Review Stop R
Sequence Number 1
Notes
Date Text
2002-10-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE THE MINIMUM ELEVATION IS 7.5
 FEET. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED FOR ADDITION.
 THE CITY CODE OF WPB REQUIRES ALL NEW
 CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT
 OF ANY EXISTING RESIDENTIAL STRUCTURE TO
 HAVE THE LOWEST FLOOR ELEVATED TO SIX
 INCHES ABOVE THE BASE FLOOD ELEVATION.
 PLEASE INDICATE THE FLOOR ELEVATIONS ON
 THE PLANS OR SURVEY.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WINDOWS
 - EXTERIOR DOORS
  
 5) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 6) SLEEPING ROOMS ARE REQUIRED TO HAVE
 AT LEAST ONE EXTERIOR EMERGENCY ESCAPE
 AND RESCUE OPENING, PER FBC 1005.4. THE
 NET CLEAR OPENING AREA AND DIMENSIONS
 MUST COMPLY WITH FBC SEC.1005.4.4. THE
 SECOND FLOOR BEDROOMS DO NOT COMPLY.
  
 7) INDICATE ACCESS TO ATTIC SPACE AS
 REQUIRED BY FBC SEC. 2309.6.
  
 8) PLEASE CLARIFY THE WINDOWS THAT HAVE
 BEEN DRAWN IN ON THE PLANS. CHANGES MUST
 BE SIGNED AND DATED BY THE DESIGNER OF
 RECORD. INDICATE WINDOW SIZES AND TYPES.
  
 9) THE ADDITION OF THESE WINDOWS EXCEED
 THE PERCENT OF WALL AREA ALLOWED AS
 OPENINGS BY TABLE 600 FOR THE FIRST AND
 SECOND FLOOR OF THE SOUTH ELEVATION.
  
 10) THE NORTH ELEVATION ON SHEET A-3
 SHOWS A WINDOW WITH A "C" DESIGNATION
 AND THERE IS NO "C" LISTED IN THE WINDOW
 SCHEDULE. PLEASE CLARIFY.
  
 11) SHEET A-5 LISTS SLOPE ON BALCONY AS
 1/4" PER FOOT AND TOP CUT OF JOISTS IS
 INDICATED TO PROVIDE 1/8" PER FOOT SLOPE
 PLEASE CLARIFY. NOTE: 1/4":12 SLOPE IS
 REQUIRED FOR MODIFIED ROOFING.
  
 12) IF STORM PANELS ARE BEING USED,
 PLEASE NOTE ON THE PLANS THAT ADEQUATE
 SUBSTRATE WILL BE PROVIDED AT GLAZED
 OPENINGS FOR THE ATTACHMENT OF STORM
 PANELS.
  
 13) FBC SEC. 1909.3 REQUIRES WELDED WIRE
 MESH TO BE SUPPORTED AT SPACINGS NOT TO
 EXCEED 3 FEET. PLEASE INDICATE THIS ON
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202