Plan Review Notes
Plan Review Notes For Permit 02090639
Permit Number 02090639
Review Stop M
Sequence Number 1
Notes
Date Text
2002-09-27 00:00:00DENIED:
  
 MECHANICAL PERMIT REQUIRED.
  
 PLEASE PROVIDE DUCT SIZE AND CFM
 DISTRIBUTION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 AS PER 2001 FBC(M) 1108.1, REFRIGERANT
 LINES SHALL BE TESTED.TEST SHALL BE
 PERFORMED WITH AN INERT DRIED GAS
 INCLUDING, BUT NOT LIMITED TO, NITROGEN
 & CARBON DIOXIDE 2001 FBC(M) 1108.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.