2002-09-25 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE NOTE ALL CIRCUITING NEEDS
 TO BE ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.215-5
  
 2)NOTE: PLEASE NOTE SIZING OF OCP FOR
 AHU. PER 424-3. PLEASE NOTE MIN OF 125%
 SHOWN AS 2P50 FOR 10KW?
  
 3)NOTE : PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600-5
  
 4)NOTE: PLEASE NOTE LOADS ON BRKRS ON
 PANEL SCHEDULE NEED TO CORRELATE WITH
 MAX OCP. PLEASE NOTE #12 W/ 25 BRKR?
 #6 W/ 24KW LOAD ON 2P-50 FOR X-RAY DISC.
 PLEASE NOTE X-RAY DISC IS SHOWN AS 100A
 ON PLANS??
  
 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%. PER
 215-3,230-42.
  
 6)NOTE: PLEASE CLARIFY SHOW WINDOW J-BOX
 ? WINDOW RECEPT? 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372