Plan Review Notes For Permit 02090419 |
Permit Number |
02090419 |
|
Review Stop |
B |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2004-04-08 00:00:00 | THE SCOSTA STEEL ROOF TRUSSES ARE | | REQUIRED TO BE REVIEWED BY THE ENGINEER | | OF RECORD BEFORE SUBMITTING TO THE CITY. | | | | THE ENGINEERING SHOWN AS STANDARD TRUSS | | DETAILS DATED 2/9/04 ISNOT SIGNED AND | | SEALED WITH THE ORIGINAL SIGNATURE AND | | EMBOSSED SEAL. | | | | THE TRUSS ENGINEERING SHEETS SHOW | | BEARING AREAS FOR THE INDIVIDUAL | | TRUSSES TO BE DIFFERENT THAN THOSE | | SHOWN ON THE PLANS IN SECTIONS 1 AND 3, | | SHEET S8. |
|