2004-07-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE SPECS SHEETS,
 PLANS AND LOAD CALCULATIONS.
  
 SOME ARE SHOWN ON PANEL SCHEDULES ETC
 AS 8.5KW AS SHOWN ON SPEC SHEET.
 SOME ARE SHOWN AS 8KW?
 LOAD CALCULATIONS INDICATE 8KW ALSO?
  
 2)NOTE: PLEASE SEE SPEC SHEET SUBMITTED
 INDICATES UNITS AS BEING 220V. PLEASE
 SEE THIS IS A 2089 VOLT SERVICE.
 PLEASE SEE SPEC SHEET MENTIONS THAT 208V
 UNITS ARE AVAILABLE. PLEASE VERIFY
 VOLTAGE ON NAMEPLATE ON UNIT. IF UNITS
 ARE RATED FOR 220V AS SHOWN ON SPEC
 SHEETS AND SERVICE IS 208V, UNITS WILL
 HAVE TO BE CHANGED.
  
 PLEASE VEROFY ALL OF THE ABOVE AND
 CORRELATE PLANS ETC.
  
 PLEASE NOTE: AS OF THIS REVIEW, A SIGNED
 SEALED NOTORIZED LETTTER HAS NOT BEEN
 RECEIVED FROM ARCH FOR LEGAL SIGNATURE
 VERIFICATION TO BE PLACED IN SIGNATURE
 FILE. SIGNATURE ON PLANS HAVE NOW
 CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]