Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop P
Sequence Number 5
Notes
Date Text
2004-07-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) FROM PREVIOUS REVIEW: NUMBER FROM THE
 PAST REVIEW WILL BE USED TO AVOID CONFU-
 SION.
 5) SHT P-4 SANT. RISER DIAGRAM, SHOW THE
 STANDPIPES AND CLEANOUTS REQUIRED BY
 SECTIONS 1002.1, 802.4 AND 708.10. THE
 CLEANOUTS SHALL BE 4' ABOVE THE FLOOR
 FOR ACCESS.
 6) SHT P-5 WATER RISER DIAGRAM SHALL RE-
 FLECT THE FLOOR PLAN, AND HOW THE WATER
 PIPING HAS BEEN INSTALLED. EXAMPLE FIRST
 UNIT ON SECOND FLOOR SHOWS LAV, WC, LINE
 TO KITCHEN SINK, TUB, THEN INSTA-HOT ON
 THE FLOOR PLAN BUT SHOWS INSTA-HOT, LAV,
 W/C, TUB, THEN KITCHEN SINK. PLEASE
 CORRELATE RISER DIAGRAM & FLOOR PLAN AND
 SHOW RISER AS A REFLECTION OF ACTUAL IN-
 STALLATION. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]