Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop M
Sequence Number 5
Notes
Date Text
2005-02-09 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLAN SHEET A-1 INDICATES AIR
 EXCHANGE UNIT.PLAN REFERENCES
 MECHANICAL DRAWING WHICH HAS NOT BEEN
 REVISED.PLEASE PROVIDE MECHANICAL
 REVISION CLARIFY "AIR EXCHANGE UNIT".
 IS THIS AN EXHAUST OR INTAKE OR BOTH?
 PLEASE NOTE, FRESH AIR INTAKES THAT
 FRONT A STREET OR PUBLIC WAY SHALL BE A
 MINIMUM OF 10FT REQUIRED TO THE
 CENTERLINE OF THE PUBLIC WAY.
  
 EXHAUST SHALL NOT DISCHARGE ONTO WALKWAY
 OR IN A MANNER THAT WILL CAUSE A
 NUISANCE PER 2001 FBC(M)401.6
  