2004-06-23 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE 422.13, MIN OCP FOR
 WATER HEATING UNIT IS TO BE A MIN OF
 125% OF NAMEPLATE KW.
 PLEASE ADJUST OCP/ AWG.
 SHOWS 30A, #10
  
 2)NOTE: PLEASE SEE "INSTA-HOTS" THAT
 WERE WATER HEATERS HAVE NOW BEEN MOVED
 FROM MECH/AREA RMS TO CLOTHES CLOSET.
 THIS IS NOT PERMITTED.
 422.17
  
 PLEASE ALSO SEE PLUMB NOTE PERTAINING
 TO ARCH'S LEGAL SIGNATURE.
 PLEASE PROVIDE LETTER AS REQUESTED FOR
 FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  