Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop B
Sequence Number 5
Notes
Date Text
2003-06-17 00:00:00SHEET S1 REVISIONS DATED 6/11/03 AND
 "FOOTERS AND AERIAL FACADE EASEMENT
 AGREEMENT"
  
 PLEASE PROVIDE STRUCTURAL CALCULATIONS
 FOR THE PROPOSED CHANGE OF THE
 FOUNDATIONFROM 81"W X 20"D CONTINUOUS
 FOOTING ON 7500 PSF SOIL TO THE 44"W X
 24"D CONTINUOUS FOOTING FOR AN
 UNDECLARED SOIL BEARING PRESSURE.
  
 PLEASE REVISE THE PAGES AND SECTIONS OF
 THE PLANS THAT WILL BE EFFECTED BY THIS
 CHANGE, SUCH AS, BUT NOT LIMITED TO
 SHEETS S6, S7 & S8.
  
 PLEASE PROVIDE A DETAIL FOR LOCATING
 THE WALL ON THE FOOTING SO AS TO ENSURE
 THE 1.34' EASEMENT AND DEPTH OF TOP OF
 FOOTING AS DESCRIBED IN THE 4/28/03
 AGREEMENT WITH THE CITY.
  
 PLEASE PROVIDE THE PLANS CALLED FOR IN
 ITEM #2 OF THE AGREEMENT.