Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop P
Sequence Number 4
Notes
Date Text
2004-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 NEC-99
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS P-2 & P-3 INSTA HOTS NOT APPROV-
 ED IN CLOSETS. NEC 99 SECTION 422-17.
 2) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR INSTA-HOTS. SECTION 303.4.
 3) SHTS P-2, P-3, & P-4 FLOOR DRAINS IN
 THE LAUNDRY SHALL BE 3" MINIMUM. SECTION
 412.4. CHANGE RISER DIAGRAM TO REFLECT
 THIS ALSO.
 4) SHT P-4 DEEP-SEAL TRAP OR TRAP PRIMER
 REQUIRED PER SECTION 1002.4. INDICATE
 ONE OR THE OTHER ON NOTE #16 PLUMBING
 SPECIFICATIONS.
 5) SHT P-4 SANT. RISER DIAGRAM, SHOW THE
 STANDPIPES AND CLEAROUTS REQUIRED BY
 SECTIONS 1002.1, 802.4 AND 708.10. THE
 CLEANOUTS SHALL BE 4' ABOVE THE FLOOR
 FOR ACCESS.
 6) SHT P-5 INSTA-HOTS ARE NOT SHOWN AS
 LOCATED IN THE SAME LOCATION AS THE
 WATER HEATERS WERE LOCATED. REVISE THE
 WATER RISER DIAGRAM TO REFLECT THE FLOOR
 PLAN FOR THE NEW LOCATION OF THE INSTA-
 HOTS. SHOW THE LOCATION OF THE REQUIRED
 WATER HAMMER ARRESTORS ON THE NEW RISER
 DIAGRAM. SECTION 104.2.1
 7) THE SIGNATURE OF THE ARCHITECT IS RE-
 QUIRED PER FAC 61G1-16.003 & FS 481.2055
 INITIALS ARE NOT ACCEPTABLE. - PROVIDE
 A SIGNED, SEALED, DATED, AND NOTORIZED
 LETTER INDICATING THAT THIS IS YOUR LEG-
 AL SIGNATURE FOR OUR ARCHITECT/ENGINEER
 SIGNATURE FILE. - THIS HAS BEEN REQUEST-
 ED PREVIOUSLY PER DEWEY PALMER, ELECTRI-
 CAL PLAN REVIEWER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]