2003-03-10 00:00:00 
  
 RESPONSE TO COMMENTS #4 RATED CHASE
 DETAIL ON PLAN SHEET A-5.DETAIL ONLY
 INDICATES 1 SIDE OF THE WALL.PLEASE
 PROVIDE DETAIL OF A PLAN VIEW AS TO THE
 ASSEMBLY AT THE CORNER OF THE SHAFT.
  
 1.PLAN SHEET M-1, 16" X 12" FRESH AIR
 DUCT DOWN FROM ROOF TOP FOR FUTURE FRESH
 AIR CONNECTION SHALL BE IN A SHAFT
 INDEPENDANT FROM THE REFRIGERANT
 ENCLOSURE AS PER NFPA 90A 3-3.4.3.
  
 2.PLAN SHEET M-2, UNIT A, FRESH AIR
 COMMENT INDICATES FRESH AIR DUCT IN 1
 HR FIRE RATED CHASE WITH FIRE DAMPER AT
 THE CHASE PENETRATION SEE DETAIL.
 DETAIL DOES NOT SHOW A FIRE DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.