Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop B
Sequence Number 22
Notes
Date Text
2005-06-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IT IS NOT CLEAR WHAT DESIGN
 PROFESSIONAL IS CERTIFYING THE STRENGTH
 OF THE DESIGN.NO TITLE BLOCK,
 ENGINEERED CALCULATIONS, DESIGN CRITERIA
 PER FBC (FBC1608.2.1(1-3),
 FBC1608.2.2(1-4))OR SEAL WAS PROVIDED.
  
 2.) THE RAILING SHOPS DO NOT HAVE THE
 JOB NAME ON THEM.WHERE WILL THIS BE
 INSTALLED?
  
 3.) PAGE 1, PROVIDE HANDRAIL HEIGHT
 FBC1007.5.HANDRAILS REQUIRED BOTH
 SIDES.
  
 4.)FBC1007.5.5, HANDRAIL SHALL
 CONTINUE TO SLOPE FOR A DISTANCE OF
 DEPTH OF ONE RISER AT THE BOTTOM.
  
 5.)PAGE 2, DIMENSIONS REQUIRED BY
 FBC1015 ARE NOT ON THE PLAN.WHAT IS
 THE LOCATION FOR THE HANDRAIL SHOWN AT
 THE BOTTOM OF PAGE 2?
  
 6.)PAGE 3 GUARDRAIL APPEARS TO BE
 DESIGNED WITHOUT THE REQUIREMENT (REJECT
 A 4" OBJECT BETWEEN PICKETS) FBC1015.3.
 PLEASE GIVE LOCATIONS FOR THE
 RAILINGS/GUARDRAILS SUBMITTED.
  
 7.)DESIGN CRITERIA ON COVER SHEET IS
 NOT COMPLIANT FOR EITHER HANDRAILS OR
 GUARDRAILS.
  
 8.)HANDRAILS REQUIRED BOTH SIDES,
 FBC1007.5.2.
  
 9.)ON THE MULLION NOA, PLEASE INDICATE
 WHICH PRODUCT(S) YOU ARE USING.NOT ALL
 ARE COMPLIANT FOR THE SIZES TO BE
 INSTALLED.
  
 10.) A REVISION FEE WAS CHARGED FOR THE
 PRODUCT APPROVALS (CHANGE FROM APPROVED
 PLAN/SPEC).
  
  