2005-06-01 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)IT IS NOT CLEAR WHAT DESIGN |
| PROFESSIONAL IS CERTIFYING THE STRENGTH |
| OF THE DESIGN.NO TITLE BLOCK, |
| ENGINEERED CALCULATIONS, DESIGN CRITERIA |
| PER FBC (FBC1608.2.1(1-3), |
| FBC1608.2.2(1-4))OR SEAL WAS PROVIDED. |
| |
| 2.) THE RAILING SHOPS DO NOT HAVE THE |
| JOB NAME ON THEM.WHERE WILL THIS BE |
| INSTALLED? |
| |
| 3.) PAGE 1, PROVIDE HANDRAIL HEIGHT |
| FBC1007.5.HANDRAILS REQUIRED BOTH |
| SIDES. |
| |
| 4.)FBC1007.5.5, HANDRAIL SHALL |
| CONTINUE TO SLOPE FOR A DISTANCE OF |
| DEPTH OF ONE RISER AT THE BOTTOM. |
| |
| 5.)PAGE 2, DIMENSIONS REQUIRED BY |
| FBC1015 ARE NOT ON THE PLAN.WHAT IS |
| THE LOCATION FOR THE HANDRAIL SHOWN AT |
| THE BOTTOM OF PAGE 2? |
| |
| 6.)PAGE 3 GUARDRAIL APPEARS TO BE |
| DESIGNED WITHOUT THE REQUIREMENT (REJECT |
| A 4" OBJECT BETWEEN PICKETS) FBC1015.3. |
| PLEASE GIVE LOCATIONS FOR THE |
| RAILINGS/GUARDRAILS SUBMITTED. |
| |
| 7.)DESIGN CRITERIA ON COVER SHEET IS |
| NOT COMPLIANT FOR EITHER HANDRAILS OR |
| GUARDRAILS. |
| |
| 8.)HANDRAILS REQUIRED BOTH SIDES, |
| FBC1007.5.2. |
| |
| 9.)ON THE MULLION NOA, PLEASE INDICATE |
| WHICH PRODUCT(S) YOU ARE USING.NOT ALL |
| ARE COMPLIANT FOR THE SIZES TO BE |
| INSTALLED. |
| |
| 10.) A REVISION FEE WAS CHARGED FOR THE |
| PRODUCT APPROVALS (CHANGE FROM APPROVED |
| PLAN/SPEC). |
| |
| |