2005-04-28 00:00:00 | ****CORRECTIONS**** | | REVISED C1, C2, A1 | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)THE STAIR HANDRAIL IS TO BE IN | | COMPLIANCE WITH FBC1007.5.5, SHALL | | EXTEND 12" BEYOND THE TOP RISER AND THE | | DISTANCE OF ONE TREAD BEYONE THE BOTTOM | | RISER.ALSO SEE FBC CHAPTER 11, FIGURE | | 19. | | | | 2.) SHOW MANEUVERING CLEARANCE FOR THE | | FRONT DOOR, FBC11 FIGURE 25. | | | | 3.) THE HANDRAIL FOR THE RAMP IS TO | | COMPLY WITH FBC1013.7. | | | | 4.)THE RAMP IS TO HAVE HANDRAILS IN | | COMPLIANCE WITH 1013.7 AND EDGE | | PROTECTION 1013.8, 1013.8.2. | | | | 5.)RISERS TO BE A MINIMUM OF 4".A1 | | SHOWS 4" RISERS BUT C1 SHOWS AN | | ELEVATION CHANGE FROM THE LANDING TO THE | | FINISHED FLOOR OF .65', WHICH IS 7.8" | | FOR THE TWO RISERS SHOWN.FBC1007.3. | | | | 6.)SHOW TREAD DEPTH. |
|