2003-01-22 00:00:00DENIED:
  
 1.PLAN SHEET M-1 DETAIL-CONDENSATE
 DRAIN TO SINK AND VENTS, CONDENSATE
 SHALL TERMINATE INTO STORM DRAIN OR
 INDEPENDENT DRYWELL. (SEE COMMENT #6,
 PLUMBING).
  
 2.EXHAUST FOR THE GARAGE & DUMPSTER /
 RECYCLING AREA SHALL NOT DISCHARGE ONTO
 WALKWAY, 2001 FBC(M) 401.5.2.
  
 3.CLARIFY GARAGE EXHAUST - NOTE ON
 PLAN SHEET M-5 EXHAUST FAN SCHEDULE
 CONTINUOUS OPERATION, WILL THIS BE TIED
 TO EMERGENCY POWER?
  
 4.PLEASE CLARIFY PLAN SHEET M-2 FRESH
 AIR DOWN FROM ROOFTOP INTAKE IN FIRE
 RATED CHASE AND DETAIL OF THE AHU
 ON PLAN SHEET M-5 INDICATES A FIRE
 DAMPER AT THE FLOOR PENETRATION.2001
 FBC(M) 607.4, FIRE DAMPERS CAN ONLY BE
 UTILIZED WHEN PENETRATING ONE FLOOR
 ONLY, DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE IN A RATED SHAFT.PLEASE
 PROVIDE DETAIL OF SHAFT & UL #.
  
 4.DRYER EXHAUST SHALL BE NON-SCREENED
 WITH A BACKDRAFT DAMPER.2001 FBC(M)
 504.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.