Plan Review Notes For Permit 02090419 |
Permit Number |
02090419 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-01-22 00:00:00 | DENIED: | | | | 1.PLAN SHEET M-1 DETAIL-CONDENSATE | | DRAIN TO SINK AND VENTS, CONDENSATE | | SHALL TERMINATE INTO STORM DRAIN OR | | INDEPENDENT DRYWELL. (SEE COMMENT #6, | | PLUMBING). | | | | 2.EXHAUST FOR THE GARAGE & DUMPSTER / | | RECYCLING AREA SHALL NOT DISCHARGE ONTO | | WALKWAY, 2001 FBC(M) 401.5.2. | | | | 3.CLARIFY GARAGE EXHAUST - NOTE ON | | PLAN SHEET M-5 EXHAUST FAN SCHEDULE | | CONTINUOUS OPERATION, WILL THIS BE TIED | | TO EMERGENCY POWER? | | | | 4.PLEASE CLARIFY PLAN SHEET M-2 FRESH | | AIR DOWN FROM ROOFTOP INTAKE IN FIRE | | RATED CHASE AND DETAIL OF THE AHU | | ON PLAN SHEET M-5 INDICATES A FIRE | | DAMPER AT THE FLOOR PENETRATION.2001 | | FBC(M) 607.4, FIRE DAMPERS CAN ONLY BE | | UTILIZED WHEN PENETRATING ONE FLOOR | | ONLY, DUCTS PENETRATING MORE THAN 1 | | FLOOR SHALL BE IN A RATED SHAFT.PLEASE | | PROVIDE DETAIL OF SHAFT & UL #. | | | | 4.DRYER EXHAUST SHALL BE NON-SCREENED | | WITH A BACKDRAFT DAMPER.2001 FBC(M) | | 504.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|