Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop E
Sequence Number 2
Notes
Date Text
2003-01-29 00:00:00*************** UNSAT ****************
  
 PLEASE SEE THE FOLLOWING NOTES, THERE
 ARE NOTES FROM FIRST TWO REVIEWS THAT
 WERE NOT ADDRESSED. PLEASE SEE THE
 ATTACHED LETTER WITH RESPECT TO DESIGN
 PROFESSIONALS UNDER FS.553-80(2)(B).
 THIS IS THE 3RD TIME THESE PLANS HAVE
 BEEN IN FOR REVIEW.
  
 1)NOTE: PLEASE SEE PANEL "E", SHOWN AS
 30 CIRCUIT AND 24 CIRCUIT. PLEASE REVISE
  
 2)NOTE: IT IS NOTED THAT THERE IS A NOTE
 MENTIONING ALL EM/EX LTS TO BE WIRED ON
 SAME BRANCH CIRCUIT AHEAD OF SWITCHING.
 HOWEVER PLAN CIRCUITING DOES NOT
 CORRELATE WITH THIS NOTE??
  
 3)NOTE: PLEASE SUBMIT AND SHOW ALL AIC
 RATINGS FOR ALL NEW EQUIPMENT BEING
 INSTALLED. MAINS, BRKRS, PANELS ARE
 ALL TO BE RATED FOR THE AVAIABLE FAULT
 CURRENT. 110-9
  
 4)NOTE; PLEASE SEE SD IN UNIT "B",
 SHOWN IN KITCHEN AND W/IN 3'OF BATHROOM
 DOOR. PLEASE RELOCATE TO A MIN OF 3'
 FROM BATH DOOR AND OUT OF KITCHEN.
 SD MAY BE MOVED JUST INTO LIVING ROOM
 AREA. NFPA-72 8-1.4.1.6
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210-12. IT WAS NOTED ON PLAN BUT
 NEEDS TO BE ON PANEL SCHEDULES.
  
 6)NOTE: PLEASE ADDRESS COMMENT FOR FHAR
 24 CFR 100.205. REQ`MENTS ARE TO BE
 NOTED ON PLANS. RECEPT AND SWITCH HEIGHT
 (S) ARE 18 AND 48" WHICH CONFORM, BUT
 THERE ARE OTHER REQ`MENTS. PLEASE NOTE
 ON PLANS FHAR.
  
 7)NOTE: PLEASE CLARIFY WHERE LOAD
 CALCULATIONS ARE FOR HOUSE PANELS.??
 215-5
  
 8)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND HOUSE PANEL. SIZE PER 250-122
  
 9)NOTE: PLEASE SEE PLANS, PANEL SCHEDULE
 -S AND RISER DIAGRMA DO NOT INDICATE
 HOW PANEL "E" IS FED?? PLEASE REVISE.
 NOT SHOWN COMING FROM PANEL HS?
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, OR IF A MEETING IS DESIRED
 TO GO OVER COMMENTS, PLEASE CALL.
  
 DEWEY PLAMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372