2004-06-30 00:00:00 | ****CORRECTIONS**** |
| REVISION DATED 6/22/04, SHEETS A1, A2, |
| A3, A5, A6, A7 |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)NO CHANGES HAVE BEEN INDICATED ON |
| THE REVISED SHEETS.ALSO, THERE IS |
| A REVISION DATE OF 2-5-03 WHICH IS NOT |
| INCLUDED.ALL CHANGES ARE TO BE |
| CLEARLY INDICATED WITH CLOUDS AND/OR |
| TRIANGLES. |
| |
| 2.) THIS CHECKLIST INCLUDES SOME OF |
| THE CHANGES FROM THE APPROVED SET OF |
| PLANS AS A COURTESY BUT IS NOT INTENDED |
| TO BE ALL INCLUSIVE.IT IS THE |
| ARCHITECT'S RESPONSIBILITY TO INDICATE |
| ALL REVISIONS FOR A COMPLETE REVIEW. |
| |
| 3.)SOME CHANGES APPEAR TO AFFECT OTHER |
| SHEETS WHICH HAVE NOT BEEN REVISED (SITE |
| PLAN, FIRE SPRINKLER, ELECTRIC, ????). |
| ADDRESS. |
| |
| 4.)DUMPSTER AREA IS NEW.HAVE PRODUCT |
| APPROVALS FOR THE LOUVERED DOORS BEEN |
| SUBMITTED? IT WAS SHOWN AS A MECHANICAL |
| ROOM PREVIOUSLY, WAS MECHANICAL REVISED? |
| THE LOUVERED DOOR IS TO COMPLY WITH |
| FBC705.1.1.2. |
| |
| 5.)ACCESSIBILITY DETAILS ARE NOW |
| MISSING FROM REVISED SHEETS A2 AND A3. |
| THEY MAY BE SUBMITTED AS A SEPARATE |
| SHEET. |
| |
| 6.)SHEET A5, THE IMPACT GLASS ON THE |
| FIRST FLOOR HAS BEEN CHANGED TO NON- |
| IMPACT WITH SHUTTERS.WHERE WILL THE |
| SHUTTERS BE STORED, AND IN WHAT MANNER? |
| IF STORED VERTICALLY, PROVIDE A DETAIL |
| FOR THE RACK. |
| |
| 7.)THE WINDOW AND DOOR SCHEDULES |
| HAVE CHANGED.SHEET A6 ALSO HAS |
| WINDOW AND DOOR CHANGES.ALL CHANGES |
| SHOULD BE CLOUDED. |
| |
| 8.)THE BUILDING FOOTPRINT AND DOOR |
| LOCATIONS NO LONGER MATCH THE APPROVED |
| SITE PLAN.REVISE SP1 FOR ZONING |
| REVIEW.AREA TOTAL FOOTAGE ALSO APPEARS |
| TO HAVE CHANGED, PLEASE REVISE. |
| |
| 9.)CONTACT IMPACT FEES AT 233-5025 |
| TO DETERMINE IF AN IMPACT FEE REVIEW |
| IS REQUIRED DUE TO THE SMALL INCREASE |
| IN SQUARE FOOTAGE. |
| |
| 10.) DOOR #1 MAY NEED TO COMPLY WITH |
| FBC11-4.13.5 (DOOR CLEARANCE, |
| ACCESSIBILITY).EITHER THIS DOOR IS |
| TO COMPLY WITH THIS CODE SECTION OR |
| AN ALTERNATE DOOR WHICH DOES COMPLY |
| IS REQUIRED. |