2002-10-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| |
| 1) SHT A-1 A DRINKING FOUNTAIN IS REQUI- |
| RED PER TABLE 403.1 |
| 2) SHTS A-2, A-3, & A-4, SHOW COMPLIANCE |
| 0F FAIR HOUSING GUIDELINE REQUIREMENTS |
| 1 THRU 7. INDICATE SPECIFICATION "A" OR |
| "B" BATHROOMS FOR ALL UNITS. SHOW BACK- |
| ING PER REQUIREMENT 6. SHOW CLEAR FLOOR |
| SPACE FOR ALL KITCHEN AND BATHROOM FIX- |
| TURES. INDICATE IF THERE WILL BE KNEE |
| SPACE AT LAV'S OR NOT. IF NOT, (PARALLEL |
| APPROACH), THE LAV WILL BE CENTERED IN |
| THE 48" CLEAR FLOOR SPACE. |
| 3) SHT A-5 A DRINKING FOUNTAIN SHALL BE |
| REQUIRED IN OFFICE. TABLE 403.1 |
| 4) SHT A-8 PLEASE PROVIDE CALCULATIONS |
| FOR PRIMARY AND SECONDARY ROOF DRAINS |
| PER SEC'S 1106 AND 1107. SHOW AREA FOR |
| ALL VERTICAL WALLS ADDED TO CALCULATIONS |
| 5) SHT P-1 PLUMBING NOTES #7, AIR CHAM- |
| BERS ARE NOT APPROVED. PLEASE DELETE RE- |
| FERENCE. |
| 6) SHT P-4 PLUMBING SPECIFICATIONS #15 |
| AIR CHAMBERS ARE NOT APPROVED, PLEASE |
| DELETE REFERENCE. |
| 7) PLEASE PROVIDE A WATER RISER DIAGRAM. |
| SHOW ALL FIXTURES, AND PIPE SIZES. SHOW |
| REQUIRED WATER HAMMER ARRESTORS PER SEC. |
| 604.9. LOCATION TO BE NEAR THE FIXTURE |
| IN AN "EFFECTIVE RANGE" NOT AT TOP OF |
| RISER OR ON MAIN LINES ABOVE CEILING PER |
| PDI-WH 201 AND MANUFACTURE INSTALLATION |
| INSTRUCTIONS. |
| 8) PLEASE SUBMIT A STORM RISER DIAGRAM. |
| SHOW ALL PIPE SIZES AND SHOW SQUARE FEET |
| AS IT ACCUMULATES IN SYSTEM. INDICATE |
| WHERE STORM LINES WILL BE TIED IN OUT- |
| SIDE OF BLDG. |
| 9) PLEASE SUBMIT A CONDENSATE RISER DIA- |
| GRAM. CONDENSATE SHALL BE PIPED SEPARAT- |
| ELY OUT OF BLDG. AND TIE INTO STORM, |
| CATCH BASIN, OR DRYWELL. A RELIEF VENT |
| IS REQUIRED AS CONDENSATE EXITS BLDG. |
| 10) PLEASE SUBMIT RISERS FOR RELIEF |
| VALVE DISCHARGE, AND EMERGENCY PAN DRAIN |
| LINES. SECS. 504.7.1 & 504.8.1 - T/P |
| LINE SHALL NOT BE TRAPPED. INDICATE MAT- |
| ERIAL USED FOR RISERS. |
| 11) PROVIDE A WATER HEATER DETAIL SHOW- |
| ING COMPLIANCE WITH 607.3 THERMAL EXPAN- |
| SION CONTROL. ALSO SEE 607.3.2 |
| 12) SHT PLEASE SHOW DRAINAGE FIXTURE |
| UNITS AS THEY ACCUMULATE IN SYSTEM. |
| |
| REVIEW BY KEN STEVENS |