2002-10-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 A DRINKING FOUNTAIN IS REQUI-
 RED PER TABLE 403.1
 2) SHTS A-2, A-3, & A-4, SHOW COMPLIANCE
 0F FAIR HOUSING GUIDELINE REQUIREMENTS
 1 THRU 7. INDICATE SPECIFICATION "A" OR
 "B" BATHROOMS FOR ALL UNITS. SHOW BACK-
 ING PER REQUIREMENT 6. SHOW CLEAR FLOOR
 SPACE FOR ALL KITCHEN AND BATHROOM FIX-
 TURES. INDICATE IF THERE WILL BE KNEE
 SPACE AT LAV'S OR NOT. IF NOT, (PARALLEL
 APPROACH), THE LAV WILL BE CENTERED IN
 THE 48" CLEAR FLOOR SPACE.
 3) SHT A-5 A DRINKING FOUNTAIN SHALL BE
 REQUIRED IN OFFICE. TABLE 403.1
 4) SHT A-8 PLEASE PROVIDE CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 PER SEC'S 1106 AND 1107. SHOW AREA FOR
 ALL VERTICAL WALLS ADDED TO CALCULATIONS
 5) SHT P-1 PLUMBING NOTES #7, AIR CHAM-
 BERS ARE NOT APPROVED. PLEASE DELETE RE-
 FERENCE.
 6) SHT P-4 PLUMBING SPECIFICATIONS #15
 AIR CHAMBERS ARE NOT APPROVED, PLEASE
 DELETE REFERENCE.
 7) PLEASE PROVIDE A WATER RISER DIAGRAM.
 SHOW ALL FIXTURES, AND PIPE SIZES. SHOW
 REQUIRED WATER HAMMER ARRESTORS PER SEC.
 604.9. LOCATION TO BE NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT AT TOP OF
 RISER OR ON MAIN LINES ABOVE CEILING PER
 PDI-WH 201 AND MANUFACTURE INSTALLATION
 INSTRUCTIONS.
 8) PLEASE SUBMIT A STORM RISER DIAGRAM.
 SHOW ALL PIPE SIZES AND SHOW SQUARE FEET
 AS IT ACCUMULATES IN SYSTEM. INDICATE
 WHERE STORM LINES WILL BE TIED IN OUT-
 SIDE OF BLDG.
 9) PLEASE SUBMIT A CONDENSATE RISER DIA-
 GRAM. CONDENSATE SHALL BE PIPED SEPARAT-
 ELY OUT OF BLDG. AND TIE INTO STORM,
 CATCH BASIN, OR DRYWELL. A RELIEF VENT
 IS REQUIRED AS CONDENSATE EXITS BLDG.
 10) PLEASE SUBMIT RISERS FOR RELIEF
 VALVE DISCHARGE, AND EMERGENCY PAN DRAIN
 LINES. SECS. 504.7.1 & 504.8.1 - T/P
 LINE SHALL NOT BE TRAPPED. INDICATE MAT-
 ERIAL USED FOR RISERS.
 11) PROVIDE A WATER HEATER DETAIL SHOW-
 ING COMPLIANCE WITH 607.3 THERMAL EXPAN-
 SION CONTROL. ALSO SEE 607.3.2
 12) SHT PLEASE SHOW DRAINAGE FIXTURE
 UNITS AS THEY ACCUMULATE IN SYSTEM.
  
 REVIEW BY KEN STEVENS