2002-09-12 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FIRE ALARM SYSTEM INSTALLATION. |
| THE FIRE ALARM SYSTEM SHALL BE CLASS A |
| OR FULLY ADDRESSABLE. |
| |
| 2) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FIRE SPRINKLER SYSTEM INSTALLATION. |
| THE HYDRAULIC CALCULATIONS LISTS |
| PALM BEACH COUNTY FIRE RESCUE AS THE |
| AHJ. IT SHOULD READ WEST PALM BEACH |
| FIRE RESCUE. HOW DOES THE BACKFLOW |
| DEVICE AND FIRE DEPARTMENT CONNECTION |
| DO NOT INTERFERE WITH EXITING FROM |
| THE STAIRTOWER. |
| |
| 3) IF FUTURE SECURITY DEVICES ARE |
| INSTALLED FOR THE GARAGE HOW IS EXITING |
| GOING TO BE ACCOMPLISHED. |
| |
| 4) ELECTRONIC SWITCHES WILL BE REQUIRED |
| ON BACKFLOW DEVICE. SEE CIVIL DRAWING |
| DETAILS. |
| |
| 5) DOORS # 9 SHALL BE AT LEAST 1 1/2 |
| RATED SINCE A TWO HOUR FIRE SEPARATION |
| IS REQUIRED BETWEEN THE GARAGE AND |
| OTHER PORTIONS OF THE BUILDING. |
| |
| 6) AN EMERGENCY LIGHT FIXTURE IS |
| LOCATED OUTSIDE OF THE STAIRTOWER ON |
| PAGE E-1. |
| |
| 7) EXITS ARE TAKING PERSONS INTO A |
| MORE HAZARDOUS AREA THE GARAGE FROM |
| THE INTERIOR TENANT SPACES. |
| |
| 8) PLEASE INDICATE EXHAUST AIR CFM'S |
| FOR PARKING GARAGE MECHANICAL |
| VENTILATION. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |