Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-09-12 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INSTALLATION.
 THE FIRE ALARM SYSTEM SHALL BE CLASS A
 OR FULLY ADDRESSABLE.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 THE HYDRAULIC CALCULATIONS LISTS
 PALM BEACH COUNTY FIRE RESCUE AS THE
 AHJ. IT SHOULD READ WEST PALM BEACH
 FIRE RESCUE. HOW DOES THE BACKFLOW
 DEVICE AND FIRE DEPARTMENT CONNECTION
 DO NOT INTERFERE WITH EXITING FROM
 THE STAIRTOWER.
  
 3) IF FUTURE SECURITY DEVICES ARE
 INSTALLED FOR THE GARAGE HOW IS EXITING
 GOING TO BE ACCOMPLISHED.
  
 4) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON BACKFLOW DEVICE. SEE CIVIL DRAWING
 DETAILS.
  
 5) DOORS # 9 SHALL BE AT LEAST 1 1/2
 RATED SINCE A TWO HOUR FIRE SEPARATION
 IS REQUIRED BETWEEN THE GARAGE AND
 OTHER PORTIONS OF THE BUILDING.
  
 6) AN EMERGENCY LIGHT FIXTURE IS
 LOCATED OUTSIDE OF THE STAIRTOWER ON
 PAGE E-1.
  
 7) EXITS ARE TAKING PERSONS INTO A
 MORE HAZARDOUS AREA THE GARAGE FROM
 THE INTERIOR TENANT SPACES.
  
 8) PLEASE INDICATE EXHAUST AIR CFM'S
 FOR PARKING GARAGE MECHANICAL
 VENTILATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910