2002-09-16 00:00:00FAILED :
 1. THE EXISTING TRAFFIC SIGN AS SHOWN AT
 NW CORNER MUST BE RELOCATED PER CITY
 ENGINEER' OFFICE DIRECTION, 659-8040
 2. THE H.C PARKING CURB CUT AS SHOWN AT
 SOUTH END OF THE BUILDING IS NOT NEEDED
 IF THE CURB CUT AT THE 14' ALLEY CAN BE
 USED, VERIFY.
 3. THE TREE GREAT AS SHOWN AT SOUTH
 END OF THE BUILDING SEEMS TO BE IN
 CONFLICT WITH EXISTING CATCH BASIN AND
 PROPOSED 12" PVC ROOF DRAIN. PLEASE
 VERIFY.
 4. IS THE EXISTING POWER POLE(NORTH END)
 IN CONFLICT WITH THE BUILDING FOUNDATION
 ?IF SO COORDINATION WITH UTILITY COMPANY
 FOR RELOCATION WOULD BE REQUIRED.
 5. LOCATING THE DDCV AND RPZ IN THE SIDE
 WALK IS NOT ACCEPTABLE UNLESS APPROVED
 BY THE PUBLIC UTILITIES ENGINEEERING
 SERVICES. NOTE: FIRE SPRINKLER PLANS
 SHOWS DDCV AND CONNECTIONS IN DEFFERENT
 LOCATION, PLEASE COORDINATE.
 6. A CURB CUT FOR THE PROPOSED ROLED OUT
 DUMPSTERS WILL BE REQUIRED.
 7. SHEET 3 OF 4 SHOWS DETAILS FOR 90 DEG
 PARKING STALL STRIPPING, SHEET 2 OF 4
 SHOWS 60 DEG. PARKING STALLS.
 8. SHEET 3 OF 4 SHOWS DETAILS FOR
 EXFILTRATION TRENCH AND CONTROL
 STRUCTURE, ETC., PLEASE SHOW LOCATIONS,
 LENGTHS,ETC.,IF USED.
 9. PLEASE SHOW DETAILS FOR INSTALLATION
 OF METER BOXES IN SIDEWALK.SEE ATTACHED
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI