Plan Review Notes
Plan Review Notes For Permit 02090419
Permit Number 02090419
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-18 00:00:00******************** UNSAT ***********
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 2)NOTE: PLEASE NOTE CIRCUITING NEEDS TO
 BE SHOWN FOR ALL BRANCH CIRCUITS ON
 PLANS.
  
 3)NOTE: PLEASE NOTE EM LTS/EXITS LTS TO
 BE ON SAME AREA BRANCH CIRCUITS. PLEASE
 SEE 700-12 NEC.
  
 4)NOTE: PLEASE CLARIFY EM LT BEING SHOWN
 TIED INTO TELEPHONE LINE.? (SECOND FLOOR
  
 5)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 6)NOTE: PLEASE CLARIFY/LABEL PANEL SHOWN
 ON E-2 LAUNDRY AREA?
  
 7)NOTE: IT WAS NOTED THAT A 3/4" CONDUIT
 STUB UP FOR TELE. PLEASE NOTE AND NOTE
 ON PLANS THAT ALL LOW IS REQ`D TO BE
 PERMITTED, INSTALLED AND INSPECTED
 BEFORE CEILING IS INSTALLED.
 PLEASE NOTE, IF NOT INSTALLED BEFORE
 ROUGH, CONDUIT SHALL BE COMPLETE TO
 TELEPHONE ROOMS.
  
 8)NOTE: PLEASE NOTE CIRCUITS ARE BEING
 LABELED AS 1-POLE ON PLANS, AS 2-POLE
 ON PANEL SCHEDULES AND YET ONLY TAKING
 ONE SPACE ON PANEL?? PLEASE CORRELATE.
  
 9)NOTE: PLEASE NOTE REQ`MENTS FOR FAIR
 HOUSING. PLEASE SEE FHAR 24 CFR 100.205
 DEVICE HEIGHTS/FHA MUST BE NOTED ON PLAN
  
 10)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN COUNTERSPACE. PER 210-52-C-1.
 MISSING A FEW.
  
 11)NOTE: PLEASE NOTE A UNIT "H" BEING
 SHOWN ON PLANS AND NO LAYOUT SUBMITTED.
 PLEASE ALSO NOTE A LAYOUT FOR A UNIT "G"
 ? PLEASE SUBMIT/ CORRELATE.
  
 12)NOTE: PLEASE SUBMIT ALL PANEL SCHEDU-
 -LES.
 PLEASE ALSO NOTE PANELS ARE BEING SHOWN
 AS 24 CIR AND 30 CIR? PLEASE SEE
 PREVIOUS COMMENT ABOUT CIRCUITING NOT
 CORRELATING.
  
 13)NOTE: PLEASE NOTE SD`S ARE INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. PLEASE NOTE
 ROOMS W/ CLOSETS AND/OR BATHS ARE CON-
 -SIDERED SLEEPING ROOMS. NFPA-72 2-2.1.1
 .1.
  
 14)NOTE: ALL LOAD CALCULATIONS ARE REQ`D
 TO BE SHOWN. PLEASE NOTE ALL CONTINUOUS
 LOADS AT 125%. PLEASE SEE 220-3,220-10,
 220-11,220-13, 230-42, 215-3,, ETC.
  
 15)NOTE: PLEASE SHOW LOCATIONS OF A/C
 COND UNITS ON ELECTRICAL PLANS. ROOF TOP
 ?? PLEASE NOTE DISC`S PER 440-11 AND
 GFI PER 210-63.
  
 16)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS FOR BEDROOM RECEPTS PER 210-12.
  
 17)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW MAINS/PANELS/ BRKRS PER 110-9,
 215-5.
  
 18)NOTE: PLEASE NOTE, E-5 NOTES ALL
 WIRING TO BE MIN #12 AND PANEL SCHEDULE
 SHOWS #14 ON SOME? PLEASE CORRELATE OR
 NOTE ,, .
  
 19)NOTE: PLEASE SHOW LOCATION OF SERVICE
 PLEASE NOTE GROUPING OF MAINS PER 230-72
 IT IS NOTED TWO SEPARATE SERVICES ARE
 SHOWN ON RISER DIAGRAM. PLEASE NOTE
 THAT A SECOND SERVICE IS NOT PERMITTED
 PER 230-2.
  
 PLEASE NOTE THAT THERE MAY BE OTHER
 COMMENTS DUE TO CHANGES IN PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372