2002-09-18 00:00:00 | ******************** UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| THAT MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| 2)NOTE: PLEASE NOTE CIRCUITING NEEDS TO |
| BE SHOWN FOR ALL BRANCH CIRCUITS ON |
| PLANS. |
| |
| 3)NOTE: PLEASE NOTE EM LTS/EXITS LTS TO |
| BE ON SAME AREA BRANCH CIRCUITS. PLEASE |
| SEE 700-12 NEC. |
| |
| 4)NOTE: PLEASE CLARIFY EM LT BEING SHOWN |
| TIED INTO TELEPHONE LINE.? (SECOND FLOOR |
| |
| 5)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| ON PLANS. |
| |
| 6)NOTE: PLEASE CLARIFY/LABEL PANEL SHOWN |
| ON E-2 LAUNDRY AREA? |
| |
| 7)NOTE: IT WAS NOTED THAT A 3/4" CONDUIT |
| STUB UP FOR TELE. PLEASE NOTE AND NOTE |
| ON PLANS THAT ALL LOW IS REQ`D TO BE |
| PERMITTED, INSTALLED AND INSPECTED |
| BEFORE CEILING IS INSTALLED. |
| PLEASE NOTE, IF NOT INSTALLED BEFORE |
| ROUGH, CONDUIT SHALL BE COMPLETE TO |
| TELEPHONE ROOMS. |
| |
| 8)NOTE: PLEASE NOTE CIRCUITS ARE BEING |
| LABELED AS 1-POLE ON PLANS, AS 2-POLE |
| ON PANEL SCHEDULES AND YET ONLY TAKING |
| ONE SPACE ON PANEL?? PLEASE CORRELATE. |
| |
| 9)NOTE: PLEASE NOTE REQ`MENTS FOR FAIR |
| HOUSING. PLEASE SEE FHAR 24 CFR 100.205 |
| DEVICE HEIGHTS/FHA MUST BE NOTED ON PLAN |
| |
| 10)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| KITCHEN COUNTERSPACE. PER 210-52-C-1. |
| MISSING A FEW. |
| |
| 11)NOTE: PLEASE NOTE A UNIT "H" BEING |
| SHOWN ON PLANS AND NO LAYOUT SUBMITTED. |
| PLEASE ALSO NOTE A LAYOUT FOR A UNIT "G" |
| ? PLEASE SUBMIT/ CORRELATE. |
| |
| 12)NOTE: PLEASE SUBMIT ALL PANEL SCHEDU- |
| -LES. |
| PLEASE ALSO NOTE PANELS ARE BEING SHOWN |
| AS 24 CIR AND 30 CIR? PLEASE SEE |
| PREVIOUS COMMENT ABOUT CIRCUITING NOT |
| CORRELATING. |
| |
| 13)NOTE: PLEASE NOTE SD`S ARE INSIDE AND |
| OUTSIDE ALL SLEEPING ROOMS. PLEASE NOTE |
| ROOMS W/ CLOSETS AND/OR BATHS ARE CON- |
| -SIDERED SLEEPING ROOMS. NFPA-72 2-2.1.1 |
| .1. |
| |
| 14)NOTE: ALL LOAD CALCULATIONS ARE REQ`D |
| TO BE SHOWN. PLEASE NOTE ALL CONTINUOUS |
| LOADS AT 125%. PLEASE SEE 220-3,220-10, |
| 220-11,220-13, 230-42, 215-3,, ETC. |
| |
| 15)NOTE: PLEASE SHOW LOCATIONS OF A/C |
| COND UNITS ON ELECTRICAL PLANS. ROOF TOP |
| ?? PLEASE NOTE DISC`S PER 440-11 AND |
| GFI PER 210-63. |
| |
| 16)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| CIRCUITS FOR BEDROOM RECEPTS PER 210-12. |
| |
| 17)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW MAINS/PANELS/ BRKRS PER 110-9, |
| 215-5. |
| |
| 18)NOTE: PLEASE NOTE, E-5 NOTES ALL |
| WIRING TO BE MIN #12 AND PANEL SCHEDULE |
| SHOWS #14 ON SOME? PLEASE CORRELATE OR |
| NOTE ,, . |
| |
| 19)NOTE: PLEASE SHOW LOCATION OF SERVICE |
| PLEASE NOTE GROUPING OF MAINS PER 230-72 |
| IT IS NOTED TWO SEPARATE SERVICES ARE |
| SHOWN ON RISER DIAGRAM. PLEASE NOTE |
| THAT A SECOND SERVICE IS NOT PERMITTED |
| PER 230-2. |
| |
| PLEASE NOTE THAT THERE MAY BE OTHER |
| COMMENTS DUE TO CHANGES IN PLANS. |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |