2002-09-25 00:00:00 | DENIED: | | | | PLEASE CLAFIFY THE FOLLOWING - | | | | 1.PLAN SHEET M-2 MECH KEY NOTE 1, | | TRANSFER DUCTS REPLACING EXISTING | | SMOKE & VENTILATION AIR EXHAUST. | | CLARIFY HOW A TRANSFER DUCT WILL | | BE REPLACING A SMOKE OR EXHAUST. IS | | THE AIR BEING TRANSFERRED FROM A | | BATHROOM TO A COMMON AREA? | | | | 2.PLAN SHEET M-2 KEY NOTE 5, INSTALL | | NEW FIRE DAMPER AT THIS LOCATION. | | IT APPEARS FIRE DAMPERS ARE BEING | | INSTALLED IN FLEX DUCT.IS THIS | | CORRECT?AS PER 2001 FBC(M) 603.5.5 | | FLEXIBLE AIR DUCTS SHALL NOT PASS | | THROUGH ANY FIRE RATED ASSEMBLY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|