Date |
Text |
2002-12-30 00:00:00 | ************ UNSAT ****************** | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125% AND PLEASE RE-CONFIGURE LOAD | | SUMMARY SHOWN AND PLEASE SHOW WHERE | | THIS LOAD CALC IS SHOWN/FIGURED PER NEC | | 220. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|