Plan Review Notes For Permit 02081890 |
Permit Number |
02081890 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-17 00:00:00 | *************** NOTES/ REDLINED ******** | | | | 1)NOTE: PLEASE NOTE MISSING BATH RECEPT | | PER 210-52D | | | | 2)NOTE: PLEASE NOTE KITCHEN COUNTER- | | -SPACE OUTLETS TO MEET 210-52-C-1. | | | | 3)NOTE: PLEASE NOTE MISSING HALLWAY | | RECEPT PER 210-52H | | | | 4)NOTE: PLEASE NOTE ALL OUTLET SPACING | | TO MEET 210-52 FOR WALL SPACE. | | | | 5)NOTE: PLEASE NOTE MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | PANEL. SIZE PER 250-122 | | | | PLEASE REVISE PLANS AND SUBMIT FOR | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | -ION IS CALLED IN. IF THERE ARE ANY | | QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|