2002-09-17 00:00:00*************** NOTES/ REDLINED ********
  
 1)NOTE: PLEASE NOTE MISSING BATH RECEPT
 PER 210-52D
  
 2)NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE OUTLETS TO MEET 210-52-C-1.
  
 3)NOTE: PLEASE NOTE MISSING HALLWAY
 RECEPT PER 210-52H
  
 4)NOTE: PLEASE NOTE ALL OUTLET SPACING
 TO MEET 210-52 FOR WALL SPACE.
  
 5)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 PLEASE REVISE PLANS AND SUBMIT FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  