Plan Review Notes For Permit 02081828
Permit Number 02081828
Review Stop M
Sequence Number 3
Notes
Date Text
2003-01-17 00:00:00PROVISO:
  
 PLEASE PROVIDE SUBMITTAL OF CURBS FOR
 THE "RELOCATED" RTU'S (MINIMUM OF 8"
 FROM THE ROOF SURFACE 2001 FBC 1511.7).
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.