2002-09-06 00:00:00 | ***************** UNSAT *************** |
| |
| 1)NOTE: PLEASE NOTE PLANS ARE NOT |
| COMPLETED FOR REVIEW. PANEL SCHEDULES |
| ETC. |
| |
| 2)NOTE: PLEASE NOTE THAT ELECTRICAL |
| POWER PLANS AND RISER DIAGRAM DO NOT |
| CORRELATE. |
| |
| 3)NOTE: PLEASE NOTE SOME EQUIPMENT |
| GROUNDING CONDUCTORS SHOWN BETWEEN |
| GUTTER(S)/METER AND MAIN DISC`S. THIS |
| IS PARALLELING THE NEUTRAL WHICH IS NOT |
| PERMITTED. PLEASE SEE 250-24. |
| |
| 4)NOTE: PLEASE CLARIFY CONDUCTORS ON |
| RISER DIAGRAM. SOME SHOWN AS ALUM AND |
| OTHERS AT COPPER? PLEASE NOTE AMPERAGE |
| RATINGS OF ALUM CONDUCTORS PER 310-16 |
| SOME AREAS ON RISER MISSING CONDUCTORS/ |
| SIZES SHOWN. |
| |
| |
| 5)NOTE: PLEASE NOTE POWER PLAN SHOWS |
| A NEW SERVICE AT ONE LOCATION AND ALSO |
| SHOWS SERVICE EQUIPMENT COMING FROM |
| EXISTING PANELS THAT ARE NOT SHOWN AS |
| NEW?? PLEASE SEE PLASN AND CORRELATE. |
| |
| 6)NOTE: PLEASE CLARIFY METHOD(S) FOR |
| GROUNDING ELECTRODES?? 250-50 |
| |
| 7)NOTE: PLEASE CLARIFY LOAD CALCS |
| SHOWING "TWO PHASE"?? |
| |
| 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| PLEASE NOTE MAINS/PANELS/BRKRS ALL |
| MUST BE RATED FOR THE AVAILABLE FAULT |
| CURRENT. 110-9 |
| |
| PLEASE NOTE THAT WHEN PLANS ARE |
| COMPLETED, A FULL REVIEW CAN ONLY THEN |
| TAKE PLACE. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |