2002-09-09 00:00:00SHOW THE FIRE RATED MIXED OCCUPACCY
 SEPARATION IN ACCORDANCE WITH FBC
 704.1.1 BETWEEN THE OFFICE AREA ON THE
 EAST SIDE AND THE WAREHOUSE ON THE
 WEST.GROUP B AND GROUP S, INCLUDING
 THE DOORS.
  
 WHAT IS THE STRUCTURE "EXISTING SHED TO
 REMAIN" SHOWN ON SHEET A 2.1 AND
 ELSEWHERE?
  
 ARE THE OPENINGS TO BE CUT IN THE
 EXISTING SEPARATION WALLS TO RECEIVE
 ANY KIND OF HEADER OR LINTEL?WILL THE
 OPENING GO TO THE DECK ABOVE?PLEASE
 CLARIFY.
  
 THE ENERGY CODE CALCULATIONS ARE NOT
 SIGNED AND SEALED AND THE PLANS DO NOT
 REFLECT THE INSULATION VALUES.SEE FBC
 13-103.