Plan Review Notes For Permit 02081828 |
Permit Number |
02081828 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-09 00:00:00 | SHOW THE FIRE RATED MIXED OCCUPACCY | | SEPARATION IN ACCORDANCE WITH FBC | | 704.1.1 BETWEEN THE OFFICE AREA ON THE | | EAST SIDE AND THE WAREHOUSE ON THE | | WEST.GROUP B AND GROUP S, INCLUDING | | THE DOORS. | | | | WHAT IS THE STRUCTURE "EXISTING SHED TO | | REMAIN" SHOWN ON SHEET A 2.1 AND | | ELSEWHERE? | | | | ARE THE OPENINGS TO BE CUT IN THE | | EXISTING SEPARATION WALLS TO RECEIVE | | ANY KIND OF HEADER OR LINTEL?WILL THE | | OPENING GO TO THE DECK ABOVE?PLEASE | | CLARIFY. | | | | THE ENERGY CODE CALCULATIONS ARE NOT | | SIGNED AND SEALED AND THE PLANS DO NOT | | REFLECT THE INSULATION VALUES.SEE FBC | | 13-103. |
|