2003-03-07 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) LINE TO RANGE (180,000 BTU) IS TOO
 SMALL @ 178' DEVELOPED LENGTH. EITHER
 1-1/4" PIPE IS REQUIRED OR A 2 LB.
 SYSTEM IS REQUIRED WITH A REGULATOR AT
 THE UNION PRIOR TO ENTERING THE BLDG.
 AND AT EACH BBQ AND THE POOL HEATER.
 IF 2 LB SYSTEM USED, PLEASE PROVIDE CUT
 SHEETS FOR REGULATORS.
  