Plan Review Notes
Plan Review Notes For Permit 02081384
Permit Number 02081384
Review Stop M
Sequence Number 1
Notes
Date Text
2002-09-07 00:00:00PASS PRIVISO
 FOR UNITS C,CR,B,BR,A,AR,
 1) REFER TO SECTION 402.3.1 BATHROOM
 EXHAUST FBC.2001
 2) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 3) CONDENSATE DRAIN MUST TERMINATE MIN.
 12IN.FROM BUILDING 1503.4.4 FBC.2001
 4) NEED PRESSURE TEST ON REF.LINES
 150 PSI 1108.1 FBC.2001
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390