Plan Review Notes For Permit 02081384 |
Permit Number |
02081384 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-07 00:00:00 | PASS PRIVISO | | FOR UNITS C,CR,B,BR,A,AR, | | 1) REFER TO SECTION 402.3.1 BATHROOM | | EXHAUST FBC.2001 | | 2) NEED FRESH AIR CALCULATIONS FOR ROUGH | | INSPECTION | | 3) CONDENSATE DRAIN MUST TERMINATE MIN. | | 12IN.FROM BUILDING 1503.4.4 FBC.2001 | | 4) NEED PRESSURE TEST ON REF.LINES | | 150 PSI 1108.1 FBC.2001 | | PLAN REVIEW BY HAROLD MOSER | | (561)659-8096 EXT.8390 |
|