Plan Review Notes For Permit 02081383 |
Permit Number |
02081383 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-09 00:00:00 | MASTER PERMIT 02081383 | | | | DENIED: | | | | 1.PROVIDE OUTSIDE AIR CALCS SHOWING | | COMPLIANCE WITH 2001 FBC(M) 402.2. | | | | 2.OVERFLOW PROTECTION REQUIRED BY | | MEANS OF AUXILIARY DRAIN PAN WITH | | SECONDARY DRAIN OR FLOAT SWITCH AS | | PER 2001 FBC(M) 307.2.3 & 307.2.4. | | | | 3.CONDENSATE SHALL DISCHARGE A MINIMUM | | OF 12" AWAY FROM THE BUILDING | | STRUCTURE 2001 FBC 1503.4.4. | | | | 4.APPLIANCES SHALL NOT BE INSTALLED | | IN A LOCATION WHERE SUBJECT TO | | MECHANICAL DAMAGE UNLESS PROTECTED | | BY APPROVED BARRIERS 2001 FBC(M) | | 303.4. | | | | 5.PROVIDE A MINIMUM OF 4" CLEARANCE | | AROUND AIR HANDLING UNIT AS PER | | 2001 FBC(M) 603.1.3 #(3). | | | | PLEASE ADDRESS THE ABOVE COMMENTS ON | | THE PLAN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|