Plan Review Notes For Permit 02081323 |
Permit Number |
02081323 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-28 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THAT THE #6 GROUND BETWEEN | | THE METER AND THE MAIN DISCONNECT | | CREATES A PARALLEL PATH TO THE | | GROUNDING ELECTRODE SYSTEM WITH THE | | NEUTRAL.ALSO CLARIFY THE #6 GROUND | | SHOWN BEING RAN WITH FPL SERVICE. | | | | THE SMOKE DETECTOR SHOWN IN THE HALLWAY | | UPSTAIRS IS TO BE LOCATED AT LEAST | | 5'FROM RETURN AIR DUCTS. | | | | REVISE THE PLANS AND RESUBMIT FOR | | REVIEW. | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|