Plan Review Notes
Plan Review Notes For Permit 02081323
Permit Number 02081323
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-28 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THE #6 GROUND BETWEEN
 THE METER AND THE MAIN DISCONNECT
 CREATES A PARALLEL PATH TO THE
 GROUNDING ELECTRODE SYSTEM WITH THE
 NEUTRAL.ALSO CLARIFY THE #6 GROUND
 SHOWN BEING RAN WITH FPL SERVICE.
  
 THE SMOKE DETECTOR SHOWN IN THE HALLWAY
 UPSTAIRS IS TO BE LOCATED AT LEAST
 5'FROM RETURN AIR DUCTS.
  
 REVISE THE PLANS AND RESUBMIT FOR
 REVIEW.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW