2002-09-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02081323
 ADD:*****LIBERTY ISLES*****
 ****MASTER "B"****
 CONT: HOME DYNAMICS VICTOR GONZALEZ
 TEL: (954)275-8569
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET A-2 NOTE: MONOLITHIC CONCRETE
 FOUNDATION WITHOUT HOOKBARS DESIGNED BY
 RATIONAL ANAYLSIS, WHAT IS THE MINIMUM
 DOWEL EMBEDDMENT DEPTH WITH NO HOOK?
 GARAGE SECTION STEMWALL CONSTRUCTION,
 DO THE DOWELS REQUIRE EXTRA EMBEDDMENT
 TO REACH THE FOUNDATION PORTION OF THE
 STEMWALL CONSTRUCTION?
  
 2) 2312.2 SHEARWALL WOOD FRAME SHEAR
 WALLS OR SEGMENTS INDICATE, OPENINGS
 IN SHEAR WALLS SHALL BE SHEATHED WITH
 STRUCTURAL SHEATHING2312.2.2
  
 3) SHEET A-3 DESIGN NOTE INDICATES WIND
 ZONE OF 130 SHOULD READ 140 MPH. ALSO
 ASCE &-98.
  
 4) SHEET A-4 MEAN ROOF HEIGHT < 25'
 ROOF SHEATHING NAILING REQUIREMENT
 PALM BEACH COUNTY AMENDMENTS!!!!!
 ZONES 1 & 2 8D
 6" EDGES & 6" INTERMEDIATES
 ZONE 3
 4" EDGES & 6" INTERMEDIATES
  
 5) PROVIDE KEY PLAN FOR INSTALATION
 SCHEDULE/ STORM SHUTTERS.
 JIM WITMER
 PLAN REVIEW