2003-01-24 00:00:00REVISION TO MASTER DENIED.PLEASE
 ADDRESS THE FOLLOWING INFORMATION.
  
 1.PLANS SUBMITTED WITH THE ORIGINAL
 APPROVED SET WERE SIGNED & SEALED BY
 ARCHITECT.REVISIONS NEED TO BE SIGNED,
 SEALED, AND DATED BY ARCHITECT (PER
 CHAPTER 481 OF THE FLORIDA STATUTES).
  
 2.PLANS ARE NOT SPECIFIC.NOTES ON
 PLAN DUCTWORK TRUNK LINE & DROP LOCATION
 MAY VARY FROM PLAN - GRILLE SIZE OR FLEX
 MAY VARY TO EQUAL OR LARGER SIZES.
 TRIANGLE OR SQUARE BOX.AS PER 2001
 FBC CHAPTER 1 AMENDMENTS SECTION 104.2.1
 DRAWINGS SHALL BE SPECIFIC, & THE
 TECHNICAL CODES SHALL NOT BE CITED AS A
 WHOLE OR IN PART NOR SHALL THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
  