Plan Review Notes
Plan Review Notes For Permit 02081322
Permit Number 02081322
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-28 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THAT THE #6 GROUND RAN
 BETWEEN THE METER AND THE FIRST MEANS
 OF DISCONNECT DOES NOT COMPLY WITH
 250-6(B).
  
 ALSO PLEASE CLARIFY THE #6 SHOWN WITH
 THE FPL FEEDERS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392